Welcome to our website.

What is the reference for the separate mounting kit for LRD4369 overload...

The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx. If a separate mounting is required...

What is the Temperature Threshold at which the Cooling Fan of Altistart 48...

The Temperature Thresholds at which the Cooling Fan of Altistart 48 Soft Starter start and stop is controlled are as follows: 1. Start – Heatsink Temperature > 50°C. 2. Stop – Heatsink Temperature...

What is the thickness of the Steel sheet metal used in Okken switchboard.

The Steel sheet metal thickness used in Okken switchboard is as listed below: Okken Steel sheet metal thickness Housing Thickness mm Door 2.00mm Rear panels 1.50mm Side panels 1.50mm Roof 1.50mm...

What is the material composition of the Main Bus Bar of the Masterpact ACB?

The material composition used in the Main Bus Bar of the Masterpact Air Circuit breaker (ACB) is shown in the table attached. Note: AL/Sn5 means Aluminum connector with Sn5 coated

Learn more through our Generic Knowledge FAQsGeneral Knowledge

What is the selection criterion of Circuit Breakers for the Capacitor bank...

The selection should be done after derating the Circuit Breaker taking into consideration voltage variation and capacitors tolerances that could increase nominal current up to 1.5In. The Derating...

What is the part number of the cable used for communication between...

TSXSCPCM4030 cable is required from TSXSCP114 PCMCIA card to the Modbus branching device TSXSCA50 for connecting other RS485 device on the Modbus Network. In case TSXSCA50 Modbus branching device is...